Karakteristik Laju Pendinginan Dan Coefficient Of Performance (COP) KTE-2000EV Menggunakan Katup Ekspansi Otomatis Dan Katup Ekspansi Thermostatik

Budi Dharma

Abstract


The purpose of the study was to determine the characteristics of the cooling rate and The ideal coefficient of performance (COP) is the KTE-2000 EV refrigeration machine using an automatic expansion valve and thermostatic expansion valves. Analysis of the cooling and COP rates is ideally done by measuring changes in room temperature and plotting data on temperature and compressor pressure on the suction side and press side (suction line and discharge line)
in the P-h diagram for the type of refrigerant R-404a. The test results show the characteristics of the average KTE-2000 EV cooling rate using an automatic expansion valve is 0.035 oC / s with an ideal COP value between 1.91 to 2.02, while for the thermostatic expansion valve the cooling rate characteristics obtained are an average of 0.024 oC / s and the ideal COP value between 2.58 and 3.13.


Keywords


Automatic expansion valve, thermostatic expansion valve, COP.

Full Text:

PDF

References


Cengels, Y.A., And Boles, M.A., 2006, THERMODYNAMICS: An Engineer Approach, Fifth Edition, McGraw-Hill.

Dossat, Roy. J., 1984, Principles of Refrigeration, John Wiley & Sons Inc, New York.

Dharma, B., 2018, Analisa Komparasi Coefficient Of Performance (COP) KTE-2000EV Menggunakan Pipa Kapiler Dan Katup Ekspansi Otomatis, Ready Star, Regional Development Industry & Health Science, Technology And Art of Life, Vol. 1, No.1, ISSN 2620-6048, Medan.

Refrigeration And Air Conditioning, 2008, Electrical Engineering Indian Institute of Technology Kharagpur, India.

Fazri, A. dan Maryati, B., Analisa Karakteristik Katup Ekspansi Termostatik Dan Pipa Kapiler Pada Sistem Pendingin Water Chiller, 2015, Jurnal Teknologi Terpadu No. 1 Vol. 4, ISSN : 2338 6649, Balikpapan.

Aziz, A., 2013, Komparasi Katup Ekspansi Termostatik dan Pipa Kapiler terhadap Temperatur dan Tekanan Mesin Pendingin, Prosiding SNTK TOPI, ISSN : 1907-0500, Pekan Baru.

Suryono., Fauzan. A., dan Hoten., Hendri Van., 2009, Kaji Eksperimental Perbandingan Performansi Mesin Pendingin Kompresi Uap dengan Menggunakan Pipa Kapiler dan Katup Ekspansi, Jurnal Teknosia. 11(6): 34-39.




DOI: https://doi.org/10.30596/rmme.v1i1.2431

Refbacks

  • There are currently no refbacks.


Creative Commons License

This work is licensed under a Creative Commons Attribution 3.0 License

Jurnal Rekayasa Material, Manufaktur dan Energi  is abstracting & indexing in the following databases: 

 

Creative Commons License

This work is licensed under a Creative Commons Attribution-ShareAlike 4.0 International License.

Statcounter View My Stats RMME